Page 31 - 美国_迪创_Det-Tronics_火焰探测器_X3301_气体检测仪_PIRECL_EQP控制器_产品样本_参数表
P. 31

FANCYIND
 FANCYIND

                                                     SPECIFICATIONS                     FANCYIND

        OPERATING VOLTAGE   20 to 28 vdc filtered supply, with less than 1.4 vpp  WEIGHT  U5005:  2 pounds (0.91 kilogram).
                            at 60 to 120 Hz.                                     U5006:   13 pounds (5.9 kilograms).

        OPERATING CURRENT   U5005   Standby: 10 milliamperes.  DIMENSIONS        U5005:   L = 14.4 inches (36.6 cm)
                                    Alarm:  35 milliamperes.                              W = 5.3 inches (13.5 cm)
 FANCYIND                   U5006 FANCYIND                                       U5006: FANCYIND
                                                                                          D = 3.8 inches (9.7 cm).
                                    Standby: 10 milliamperes.
                                    Alarm:
                                                                                          L = 14.75 inches (37.5 cm)
                                           50 milliamperes.
                                                                                          W = 11.6 inches (29.5 cm)
                            Operating: –13°F to +140°F (–25°C to +60°C).
        TEMPERATURE RANGE
                            Storage:   –67°F to +185°F (–55°C to +85°C).                  D = 6.1 inches (15.5 cm).
                                                              SAMPLING TUBES     Material:  Galvanized steel tubing 3/4 inch EMT,
        HUMIDITY RANGE      0 to 90% RH non-condensing.       (U5006 ONLY)                length to be specified by customer
        (U5006 ONLY)                                                                      (1, 3, 6,or 10 feet).

        AIR VELOCITY RANGE  600 to 4000 ft/min.                                  Return tube: 12 inch standard length sampling
        (U5006 ONLY)                                                                      tube.


        SENSITIVITY RANGE   Meets  ANSI/UL268A visible smoke obscuration
        (U5006)             limits:                           ORDERING INFORMATION When ordering, please specify:

                                                                                 U5005 Smoke Detector
                            Grey smoke:  7.0% / ft maximum,                      U5006 Air Duct Smoke Detector
 FANCYIND                   Black smoke:  10.0% / ft maximum,                    When ordering the U5006, specify the air duct
                                FANCYIND
                                                                                        FANCYIND
                                     0.5% / ft minimum
                                                                                 sampling tube length required.
                                     0.5% / ft minimum.

        SENSITIVITY RANGE   2.3% obscuration.                                    The air duct sampling tube provides a cross sec-
                                                                                 tional sampling of air moving through the duct and
        (U5005)
                                                                                 is available in four lengths.  The air duct sampling
                                                                                 tube should cover the entire width of the duct,
        ALARM AND SUPER-    1.0 ampere at 30 vdc, SPST.
                                                                                 therefore, specify the shortest sampling tube that is
        VISORY RELAY CONTACT
                                                                                 at least the width of the duct to be protected. It can
        RATING
                                                                                 then be cut to the exact length at the job site.
        AUXILIARY ALARM RELAY 2.0 amperes at 30 vdc, Form C, SPDT.
                                                                                 Available duct sampling tube sizes:
        CONTACT RATING
                                                                                 Description   Model    Part Number
        FIBERGLASS          NEMA 4X. Cover is clear polycarbonate with
                                                                                 1 foot length  ST- 1   004783-001
        ENCLOSURE           closed cell neoprene gasket supplied with
                                                                                 3 foot length  ST- 3   004783-002
                                FANCYIND
                            stainless steel screws.
                                                                                        FANCYIND
 FANCYIND  CERTIFICATION    CSA Certified for Class I, Division 2,               10 foot length  ST- 10  004783-004
        (U5006 ONLY)
                                                                                                ST- 6
                                                                                                        004783-003
                                                                                 6 foot length
                            Groups A, B, C & D Hazardous Locations.
                        Detector Electronics Corporation
                        6901 West 110th Street • Minneapolis, Minnesota 55438 USA
           REGISTERED BY UL AND BSI
          ISO 9001      Operator: (952) 941-5665 or (800) 765-FIRE
               REGISTERED FIRM
            REGISTERED FIRM
           NO. A2305 • NO. 25826  Customer Service: (952) 946-6491 • Fax (952) 829-8750
                        http://www.det-tronics.com • E-mail: detronics@detronics.com  Specifications subject to change without notice.
   26   27   28   29   30   31   32   33   34   35   36