                                                                                      SPECIFICATION DATA

                                                                     Smoke Detectors for Classified Areas

                                                                                   U5005, U5006 Duct Mount



 FANCYIND                       FANCYIND                                                FANCYIND






















                              APPLICATION                                             FEATURES

           The Det-Tronics U5005 Smoke Detector is a sensitive yet  • CSA Certified for use in Class I, Division 2, Groups A, B, C
                                                                   and D hazardous locations.
           rugged, state-of-the-art protection device that is designed for  • Trouble-free photoelectric operation.
                                                                                        FANCYIND
                                FANCYIND
 FANCYIND  The detector is designed to operate effectively with both slow  • Standard 4-wire 24 vdc operation.
           classified areas in hazardous industrial and commercial locations.
           smoldering and fast burning fires.  The U5005 Smoke Detector
           includes an external alarm indicating LED, as well as alarm,
                                                                 • Designed to meet ANSI/UL 268A smoke obscuration limits.
           power supervision and auxiliary relays.  Typical applications that
           use the U5005 include:
                                                                 • 600 to 4000 ft/min airflow range (duct mount model).
           • Combustible storage facilities                      • Rugged design for environmental extremes.
           • Munitions manufacturing
                                                                 • Self-checking circuitry ensures reliable smoke detection.
           • Volatile chemical storage
           • Chemical processing plants                          • Regulation photodiode, matched to the smoke detection cir-
           • Petroleum refineries                                  cuit, adjusts output as necessary to compensate for accumu-
           • Turbine enclosures.                                   lation of contaminants or environmental variations.

                                                                 • Detector uses extensive filtering against RF and transient
           The Det-Tronics U5006 Air Duct Smoke Detector, using the tech-  interference.
           nology of the U5005 Smoke Detector mounted inside a fiberglass
           NEMA 4X enclosure, is designed to detect the presence of  • Form A (SPST) N.O. alarm relay contacts (latching) for con-
           smoke for the primary purpose of controlling blowers and  • Form A (SPST) N.C. contacts for supervision of input power.
                                                                   nection to alarm response circuitry.
           dampers in air conditioning and ventilation systems.  The unit
 FANCYIND  mounts directly to heating, ventilating, and air conditioning ducts  • Auxiliary Form C (SPDT) N.O./N.C. alarm relay for controlling
                                                                                        FANCYIND
                                FANCYIND
           and uses a cross sectional sampling tube arrangement that
           allows large volume air sampling. The U5006 includes the same
                                                                   remote annunciating devices.
           relay outputs as the U5005.
                                                                   to provide a visual indication that an alarm condition has
           The detectors are intended to be connected to a control unit and  • LED located on the outer surface of the housing is illuminated
           function as part of a fire protection system  (4-wire system, 2  occurred.
           wires for detector power and 2 wires for detector output).