Page 29 - 美国_迪创_Det-Tronics_火焰探测器_X3301_气体检测仪_PIRECL_EQP控制器_产品样本_参数表
P. 29

FANCYIND
 FANCYIND

                                                    SPECIFICATIONS                      FANCYIND

         Operating Voltage   24 Vdc. Operating range is 18 to 30 Vdc  Certification
                           Maximum ripple is 2 volts peak-to-peak.
                                                                FM         ®
         Power Consumption   2.5 watts @ 24 Vdc nominal         APPROVED
                           7.6 watts @ 30 Vdc with EOL resistor installed.
                                                              Class I, Div. 1, Groups B, C & D (T5);  DEMKO 01 ATEX 132195X
         Relays            Contacts rated 5 amperes at 30 Vdc  Class II, Div 1, Groups E, F & G (T5);  Increased Safety Model
 FANCYIND                  Fault:   FANCYIND                  Class III.                FANCYIND
                                                              Class I, Div. 2 , Groups A, B, C & D (T3);
                                                                                                       II 2 G
                                                                                                0539
                                                                                                       II 2 D
                           Fire Alarm:   — Form C (NO and NC contacts)

                                                              Class II, Div 2. Groups F & G (T3);

                                    — normally de-energized
                                                                                            Ex d e IIC T6–T5 Gb
                                                              Enclosure NEMA/Type 4X.
                                    — latching/non-latching
                                                                                            Ex tb IIIC T80°C
                                                                                            T6 (Tamb –50°C to +60°C)
                                    — Form A (NO contacts)
                                                              For FM Zone approval information, refer to
                                                                                            T5 (Tamb  –50°C to +75°C)
                                                              the X2200 instruction manual (95-8549).
                                    — normally energized
                                    — latching/non-latching
                           Auxiliary*:   — Form C (NO and NC contacts)                      IP66/IP67.
                                                                                            Flameproof Model
                                    — normally energized                                               II 2 G
                                    — latching/non-latching.                                    0539    II 2 D
                                                                                            Ex d IIC T6–T5 Gb
         Current Output*   0–20 mA (± 0.3 mA), with a maximum loop       IEC 61508          Ex tb IIIC T80°C
           (Optional)      resistance of 500 ohms from 18–19.9 Vdc,  Certified SIL 2 Capable  T6 (Tamb –55°C to +60°C)
                           600 ohms from 20–30 Vdc.
                                                              Applies to specific models –  T5 (Tamb  –55°C to +75°C)
         Temperature Range    Operating:   –40°C to +75°C (–40°F to +167°F)  Refer to the SIL 2 Certified   IP66/IP67.
                           Storage:   –55°C to +85°C (–67°F to +185°F)  X2200 Safety Manual (95-8672).
                           Hazardous location ratings from –55°C to +75°C
                           available on flameproof model.
         Humidity Range    0 to 95% relative humidity, can withstand 100%
                           condensing humidity for short periods of time.                   IECEx Certificate of Conformity
                                                              VNIIFTRI                      IECEx ULD 06.0018X
                                                              Certificate of Conformity
                           The detector has a 90 degree cone of vision
                                                                                            Ex d e IIC T6–T5 Gb

         Field of View
 FANCYIND    Source Tube   3 years. FANCYIND           85     2ExdeIICT6/T5 IP66        FANCYIND
                                                              to CUTR 012/2011
                                                                                            Ex tb IIIC T80°C

                           (horizontal) with the highest sensitivity lying along
                                                                                            T6 (Tamb = –50°C to +60°C).
                           its central axis.
                                                                                            T5 (Tamb = –50°C to +75°C).
                                                              T6 (Tamb = –55°C to +60°C)
                           Contains radioactive isotope Krypton 85 (Kr )
                                                              T5 (Tamb = –55°C to +75°C)
                                                                                            IP66/IP67.

                           14,800 Becquerels (0.4μCi).
           Calculated Activity:
                                                              – OR –
                                                                                            – OR –
                                                              1ExdIICT6/T5 IP66
         Warranty
                                                                                            Ex tb IIIC T80°C
                                                              T6 (Tamb = –55°C to +60°C)    Ex d IIC T6–T5 Gb
         Enclosure Material   Copper-free aluminum (painted) or stainless steel    T5 (Tamb = –55°C to +75°C).  T6 (Tamb = –55°C to +60°C).
                           (316/CF8M cast).                                                 T5 (Tamb = –55°C to +75°C).
                                                                                            IP66/IP67.
         Conduit Entry Size   3/4 inch NPT or M25.
                                       2
         Wiring            16 AWG or 2.5 mm  shielded cable is recommended.
                                                              VNIIPO
         Shipping Weight   Aluminum:       7 lbs. (3.2 kg)    Certificate of Conformity to technical
           (Approximate)   Stainless Steel:  14.6 lbs. (6.7 kg).  regulations, GOST R 53325-2009.
                                                                                            UL-BRHZ-0061X
         Response Characteristics                                                           Ex d e IIC T6–T5 Gb
        Very High Sensitivity                                                               T6 (Tamb = –50°C to +60°C)
                                                                                            T5 (Tamb = –50°C to +75°C)
                            Distance  Typical Response
           Fuel     Size                           Mode               VdS                   IP66/IP67
                            Feet (m)  Time (seconds)
                            85 (25.9)
                   1 x 1 foot
         n-Heptane  32 inch plume  100 (30.5)  3 2  Low Arc    Approvals to EN54-10         – OR –
                                                                                            Ex d IIC T6-T5 Gb
 FANCYIND  NOTE:   Refer to the X2200 instruction manual 95-8549 for details regarding   FANCYIND
                                FANCYIND
          Methane
                                                               See instruction manual for details.
                                                   Low Arc
                                                                                            T6 (Tamb = –55°C to +60°C)
                                                                                            T5 (Tamb = –55°C to +75°C)
              detector response.
                                                                                            IP66/IP67.
        *Auxiliary relay and 0 to 20 mA output are not available on pulse output model.
                                                                                                        Corporate Office
                                                                                         th
        Specifications subject to change without notice.                       6901 West 110  Street | Minneapolis, MN 55438 USA
                                                                                        Operator: 952.941.5665 or 800.468.3244
        All trademarks are the property of their respective owners.               Customer Service: 952.946.6491 or 800.765.3473
        © 2014 Detector Electronics Corporation. All rights reserved.       www.det-tronics.com | Email: det-tronics@det-tronics.com
   24   25   26   27   28   29   30   31   32   33   34