Page 55 - 美国_迪创_Det-Tronics_火焰探测器_X3301_气体检测仪_PIRECL_EQP控制器_产品样本_参数表
P. 55

FANCYIND

                                FANCYIND                                                FANCYIND
                                   Certificate / Certificat / Zertifikat /

                                                      DET 090204 C001


                                            Systematic Integrity: SIL 2 Capable

                                            Random Integrity: Type B Element
                                                                                        FANCYIND
 FANCYIND                       FANCYIND               AVG  and Architecture Constraints
                                                  PFD
                                                  must be verified for each application


  Pointwatch Eclipse
  Infrared Hydrocarbon               SIL 2 Capability:
                                     The product has met manufacturer design process requirements of Safety
  Gas Detector                       Integrity Level (SIL) 2. These are intended to achieve sufficient integrity
                                     against systematic errors of design by the manufacturer.
                                     A Safety Instrumented Function (SIF) designed with this product must not
  Detector Electronics               be used at a SIL level higher than stated without “prior use” justification by
  Corporation                        end user or diverse technology redundancy in the design.
  Minneapolis, MN USA
                                     IEC 61508 Failure Rates in FIT*


                                    Device                    λ        λ        λ         λ        SFF
                                                                        SU
                                                                                  DD
                                                                                           DU
                                                               SD
                                    Eclipse-PIRECL IR Gas
                                    Detector, Analog Output   118      645      1537      123     94.6%
 FANCYIND                       FANCYIND                      118      626      1322    FANCYIND
                                    Eclipse-PIRECL IR Gas
                                                                                          132
                                                                                                  94.0%
                                    Detector, Relay Output












                                     SIL Verification:

                                     The Safety Integrity Level (SIL) of an entire Safety Instrumented Function (SIF)
                                     must be verified via a calculation of PFD AVG  considering redundant
                                     architectures, proof test interval, proof test effectiveness, any automatic
         e
         e ida             ® ®       diagnostics, average repair time and the specific failure rates of all products
                ida
                                     included in the SIF. Each subsystem must be checked to assure compliance
 FANCYIND  64 N Main St         FANCYIND               9                                FANCYIND
                                     with minimum hardware fault tolerance (HFT) requirements.
                                     * FIT = 1 failure / 10  hours
          Sellersville, PA 18960

    Form     Version   Date

    C61508   2.7-2    Mar 2011                                                           Page 2 of 2