                                           Certificate / Certificat / Zertifikat /



                                                               DET 1108054 C001

                                             Systematic Capability: SC 2 (SIL 2  Capable)
                                                                                        FANCYIND
 FANCYIND                       FANCYIND                      SIL 2 @ HFT=0; Route 1          H
                                                   Random Capability: Type B Element



                                                                   and Architecture Constraints
                                                          PFD
                                                               AVG
                                                          must be verified for each application
             X3301, X3302
             Multispectrum IR               Systematic Capability:
             Flame Detectors                The Product has met manufacturer design process requirements of Safety
                                            Integrity Level (SIL) 2. These are intended to achieve sufficient integrity against
                                            systematic errors of design by the manufacturer.
                                            A Safety Instrumented Function (SIF) designed with this product must not be
                                            used at a SIL level higher than stated.
                                            Random Capability:
                                            The SIL limit imposed by the Architectural Constraints must be met for each
                                            element.
 FANCYIND                       FANCYIND                                     λ SD   λ SU FANCYIND
                                            IEC 61508 Failure Rates in FIT*


                                                                                                          SFF
                                           Device
                                                                                                    λ
                                                                                            λ
                                                                                                     DU
                                                                                             DD
                                           X3301/X3302 Relay, FW Rev K
                                                                            0
                                                                                                  116
                                                                                                          96.0%
                                                                                   359
                                                                                           2448
                                           X3301/X3302 Current, FW Rev K    1777   360     634    124     95.7%
                                           X3301/X3302 mA w/HART,           0      363     2615   133     95.7%
                                           FW Rev K
                                           X3301 Relay, FW Rev E            335    120     556    88      92.0%
                                           X3301 Current, FW Rev E          0      106     920    75      93.2%
                                           X3301 mA w/HART, FW Rev E        0      110     1146   93      93.1%
                                            * FIT = 1 failure / 10 hours
                                                              9
                                            SIL Verification:
                                            The Safety Integrity Level (SIL) of an entire Safety Instrumented Function (SIF)
                                            must be verified via a calculation of PFD AVG  considering redundant
 FANCYIND                       FANCYIND                                                FANCYIND
                                            architectures, proof test interval, proof test effectiveness, any automatic
                                            diagnostics, average repair time and the specific failure rates of all products
                                            included in the SIF. Each element must be checked to assure compliance with
                                            minimum hardware fault tolerance (HFT) requirements.


                 64 N Main St               The following documents are a mandatory part of certification:
                                            Assessment Report:  DET11-08-054 R003 V3 R1
                 Sellersville, PA 18960
                                            Safety Manual:  #95-8582, Rev 5.1 and later, or #95-8720, Rev 1.2 and later
                   T-013, V3R7
                                                                                                    Page 2 of 2